Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
Appliance for Hadoop 5 Base Cabinet Config b 53,300 2030 0.958 1828 830 See Dimensions: 42-U Cabinet
InfiniBand switch cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
InfiniBand switch Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.