Site Floor and Ceiling Height Specifications - Integrated Big Data Platforms

1700 Platform Product and Site Preparation Guide

Product
Integrated Big Data Platforms
Published
March 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
esf1471887251194.ditamap
dita:ditavalPath
1700.ditaval.ditaval
dita:id
ffn1471647521493
Product Category
Hardware
Site Feature Recommended Minimum Height Explanation
Raised floor 61.0 cm (24 in.) If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).
Ceiling 3 m (10 ft) Recommended height prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.