Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
2750 cabinet with:
  • one VMS
  • eight processing nodes
  • twelve drive enclosures, six with controllers
  • two 24-port server management Ethernet switches
  0.726 sq m

(7.8 sq ft)

751 kg

(1656 lb)

based on cabinet footprint:

1034 kg/sq m (212 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

511 kg/sq m (105 lb/sq ft)

14.7 kg/sq cm

(208 lb/sq in.)

BYNET cabinet 108-port maximum configuration:
  • two 108-Port InfiniBand switches
  • two TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

500 kg (1100 lb)

based on cabinet footprint:

688 kg/sq m (141 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

340 kg/sq m (69 lb/sq ft)

9.5 kg/sq cm

(134 lb/sq in.)

BYNET cabinet 162-port maximum configuration:
  • one 162-Port InfiniBand switch
  • three TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

396 kg

(872 lb)

based on cabinet footprint:

545 kg/sq m (112 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

269 kg/sq m (55 lb/sq ft)

7.75 kg/sq cm

(109 lb/sq in.)

  0.73 sq m

(7.8 sq ft)

420 kg

(926 lb)

based on cabinet footprint:

578 kg/sq m (119 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

285 kg/sq m (58 lb/sq ft)

8.2 kg/sq cm

(116 lb/sq in.)

Cables   Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system.
Weight and floor loading for Platform Framework Cabinets must be based on the maximum configurations supported by the platform. See the Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.