System Thermal Report - Data Warehouse Appliances

2850 Platform Product and Site Preparation Guide

Product
Data Warehouse Appliances
Published
February 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
ipe1471887155021.ditamap
dita:ditavalPath
2850.ditaval.ditaval
dita:id
ibv1471648709644
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
2850 Max Config b 50,000 1460 0.689 2179 988 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b2850 maximum configuration = 2850 with three 4+0 cliques (twelve drive enclosures, eight processing nodes), one system VMS, one KVM, two 36-port BYNET V5 InfiniBand switches, two 24-port server management switches, four PDU strips, Four 30 Amp AC feeder boxes, doors, cabinet.