System Thermal Report - Data Mart Appliances

670 Platform Product and Site Preparation Guide

Product
Data Mart Appliances
Published
June 2015
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
rac1471886432192.ditamap
dita:ditavalPath
670.ditaval.ditaval
dita:id
oiu1471648935842
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
670 Max Config b 25,000 950 0.448 1440 653 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b670 max. configuration = Three 670 systems per cabinet, each with one processing node, one disk array with two drive enclosures and 24 drives per enclosure, and one VMS; plus one KVM, two switches, and four TMSs per cabinet.