Unit | Actual Footprint Area (No Stabilizers) | Approx. Installed Weight | Distributed Floor Loading | Concentrated Floor Loading | |
---|---|---|---|---|---|
6750H/HX cabinet maximum configuration |
|
|
based on cabinet footprint: 1098 kg/sq m (225 lb/sq ft ) based on footprint plus servicing clearance required to open doors: 542 kg/sq m (112 lb/sq ft ) |
|
|
BYNET
cabinet 108-port maximum
configuration:
|
0.73 sq m (7.8 sq ft) |
500 kg (1100 lb) |
based on cabinet footprint: 688 kg/sq m (141 lb/sq ft) based on footprint plus servicing clearance required to open doors: 340 kg/sq m (69 lb/sq ft) |
9.5 kg/sq cm (134 lb/sq in.) |
|
BYNET
cabinet 162-port maximum configuration:
|
0.73 sq m (7.8 sq ft) |
396 kg (872 lb) |
based on cabinet footprint: 545 kg/sq m (112 lb/sq ft) based on footprint plus servicing clearance required to open doors: 269 kg/sq m (55 lb/sq ft) |
7.75 kg/sq cm (109 lb/sq in.) |
|
0.73 sq m (7.8 sq ft) |
420 kg (926 lb) |
based on cabinet footprint: 578 kg/sq m (119 lb/sq ft) based on footprint plus servicing clearance required to open doors: 285 kg/sq m (58 lb/sq ft) |
8.2 kg/sq cm (116 lb/sq in.) |
Vented floor tiles cannot support as much weight as solid tiles. When
moving cabinets in a computer room, replace vented floor tiles with solid floor
tiles along the path where cabinets will be rolled. Failure to do so may cause
damage or collapse of vented floor tiles, resulting in physical damage and/or bodily
injury.
Weight and floor loading for Platform Framework Cabinets must be based
on the maximum configurations supported by the platform. See the
Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.