Weight and Floor Loading - Active Enterprise Data Warehouse

6800 Platform Product and Site Preparation Guide

Product
Active Enterprise Data Warehouse
Published
February 2018
Language
English (United States)
Last Update
2018-04-19
dita:mapPath
vyt1471885165825.ditamap
dita:ditavalPath
6800.ditaval.ditaval
dita:id
jso1471649458844
Product Category
Hardware
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
6800 cabinet with one 2+1 clique (maximum configuration)
  • sixteen drive enclosures, four with controllers
  • three processing nodes
  • one VMS
  • two 36-port BYNET V5 InfiniBand switches
  • two 24-port server management Ethernet switches
  • four PDU strips
  • two AC feeder boxes
  • doors
  • cabinet
 
  • 0.73 sq m
  • (7.8 sq ft)
  • 798 kg
  • (1760 lb)

based on cabinet footprint:

1098 kg/sq m (225 lb/sq ft )

based on footprint plus servicing clearance required to open doors:

542 kg/sq m (112 lb/sq ft )

  • 15.6 kg/sq cm
  • (221 lb/sq in.)
BYNET cabinet 108-port maximum configuration:
  • two 108-Port InfiniBand switches
  • two TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

500 kg (1100 lb)

based on cabinet footprint:

688 kg/sq m (141 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

340 kg/sq m (69 lb/sq ft)

9.5 kg/sq cm

(134 lb/sq in.)

  0.73 sq m

(7.8 sq ft)

420 kg

(926 lb)

based on cabinet footprint:

578 kg/sq m (119 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

285 kg/sq m (58 lb/sq ft)

8.2 kg/sq cm

(116 lb/sq in.)

BYNET cabinet 648-port maximum configuration:
  • one 648-Port InfiniBand switch
  • one 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

563 kg

(1242 lb)

based on cabinet footprint:

775 kg/sq m (159 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

382 kg/sq m (78 lb/sq ft)

11 kg/sq cm

(154 lb/sq in.)

Weight and floor loading for Platform Framework Cabinets must be based on the maximum configurations supported by the platform. See the Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.