Unit | Actual Footprint Area (No Stabilizers) | Approx. Installed Weight | Distributed Floor Loading | Concentrated Floor Loading | |
---|---|---|---|---|---|
Appliance for
Hadoop 3 and 4 cabinet maximum configuration:
|
0.726 sq m (7.8 sq ft) |
830 kg (1828 lb) |
based on cabinet footprint: 1143 kg/sq m (234 lb/sq ft) based on footprint plus servicing clearance required to open doors: 564 kg/sq m (115 lb/sq ft) |
16.2 kg/sq cm (230 lb/sq in.) |
|
InfiniBand switch cabinet 108-port maximum
configuration:
|
0.73 sq m (7.8 sq ft) |
500 kg (1100 lb) |
based on cabinet footprint: 688 kg/sq m (141 lb/sq ft) based on footprint plus servicing clearance required to open doors: 340 kg/sq m (69 lb/sq ft) |
9.5 kg/sq cm (134 lb/sq in.) |
|
InfiniBand
switch cabinet 162-port maximum configuration:
|
0.73 sq m (7.8 sq ft) |
396 kg (872 lb) |
based on cabinet footprint: 545 kg/sq m (112 lb/sq ft) based on footprint plus servicing clearance required to open doors: 269 kg/sq m (55 lb/sq ft) |
7.75 kg/sq cm (109 lb/sq in.) |
|
0.73 sq m (7.8 sq ft) |
420 kg (926 lb) |
based on cabinet footprint: 578 kg/sq m (119 lb/sq ft) based on footprint plus servicing clearance required to open doors: 285 kg/sq m (58 lb/sq ft) |
8.2 kg/sq cm (116 lb/sq in.) |
||
Cables | Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system. |
Vented floor tiles cannot support as much weight as solid tiles. When
moving cabinets in a computer room, replace vented floor tiles with solid floor
tiles along the path where cabinets will be rolled. Failure to do so may cause
damage or collapse of vented floor tiles, resulting in physical damage and/or bodily
injury.
Weight and floor loading for Platform Framework Cabinets must be based
on the maximum configurations supported by the platform. See the
Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.