Measuring Air Flow Rate Using an Air Flow Meter and Handmade Air Capture Hood - Appliance for Hadoop

Appliance for Hadoop 3 and 4 Platforms Product and Site Preparation Guide

Product
Appliance for Hadoop
Published
March 2018
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
alw1471885284809.ditamap
dita:ditavalPath
hadoop3_4.ditaval.ditaval
dita:id
byo1471650857173
Product Category
Hardware

The following illustration shows the dimensions of a recommended air capture hood.

Handmade Air Capture Hood and Measurement Locations

  1. Make a four-sided cardboard air hood with two open ends:
    • large end: 61 cm x 61 cm (2 ft x 2 ft) (standard floor tile size)
    • small end: 30.5 cm x 30.5 cm (1 ft x 1 ft)
  2. Place the hood with the large open end over a vented floor tile. Minimize air flow leakage by sealing seams on the hood, and by pressing the hood firmly against the floor.
  3. Hold the air flow meter at the small open end of the hood, in the center, to get a reading of the air velocity.
  4. Convert the air velocity reading to the air flow rate.

    The measurement in cubic feet per minute is:

    flow rate (ft 3/min) = flow velocity (ft/min) x area (1 sq. ft on small open end of hood)