| Cabinet | Typical Heat Dissipation | Air Flow Nominal | Weight | Overall Cabinet Dimensions | ||
|---|---|---|---|---|---|---|
| BTU/Hr a | CFM | m 3/sec | lb | kg | ||
| Appliance for Hadoop 3 and 4 Base Cabinet Config b | 41,700 | 1590 | 0.750 | 1828 | 830 | See Dimensions: 42-U Cabinet |
| InfiniBand switch cabinet with 108-Port InfiniBand Switch and TMSs | 15,400 | 590 | 0.278 | 1100 | 500 | See Dimensions: 42-U Cabinet |
| InfiniBand switch cabinet with 162-Port InfiniBand Switch and TMSs | 13,700 | 520 | 0.245 | 872 | 396 | See Dimensions: 42-U Cabinet |
| InfiniBand switch Cabinet with 324-Port InfiniBand Switch |
|
|
|
926 | 420 | See Dimensions: 42-U Cabinet |
| ASHRAE Class 1 |
|
|||||
|
a 1 watt = 3.412 BTU/Hr. b Appliance for Hadoop 3 and 4 base cabinet configuration = Eighteen nodes with twenty-four storage drives and two CPUs each, one VMS, two 36-port Aster network switches, and two 24-port server management switches. |
||||||