Site Floor and Ceiling Height Specifications - Appliance for Hadoop

Appliance for Hadoop 5 Platform Product and Site Preparation Guide

Product
Appliance for Hadoop
Published
February 2018
Content Type
Product Guide
Publication ID
B035-6030-075K
Language
English (United States)
Last Update
2018-05-03
Site Feature Recommended Minimum Height Explanation
Raised floor 61.0 cm (24 in.) If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).
Ceiling 3 m (10 ft) Recommended height prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.