Phase currents are not balanced on three-phase AC feeder boxes. If you have more than one cabinet with the three-phase AC feeder box, you will need to rotate the phase connections on each outlet to minimize the aggregate site imbalance. Consult this table for how to connect the phases to the receptacle in order to rotate the phase connections.
With a three-phase Wye AC feeder box, the phase imbalance results in a current on the neutral wire.
Cabinet # | Phase #1 | Phase #2 | Phase #3 |
---|---|---|---|
Cabinet #1 | L1 | L2 | L3 |
Cabinet #2 | L3 | L1 | L2 |
Cabinet #3 | L2 | L3 | L1 |
Cabinet #4 | L1 | L2 | L3 |
Cabinet #5 | L3 | L1 | L2 |
Cabinet #6 | L2 | L3 | L1 |
Cabinet #7 | and so on | and so on | and so on |