Weight and Floor Loading - Aster Appliances

Aster Appliance 3H and 4 Platforms Product and Site Preparation Guide

Product
Aster Appliances
Published
February 2018
Language
English (United States)
Last Update
2018-04-16
dita:mapPath
vjp1471886019008.ditamap
dita:ditavalPath
aster3.ditaval.ditaval
dita:id
zua1471650759470
lifecycle
previous
Product Category
Hardware
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
Aster Appliance 3H and 4 cabinet maximum configuration:
  • one VMS
  • one KVM
  • eighteen nodes with integrated storage drives
  • two 36-port InfiniBand switches
  • two 24-port server management Ethernet switches
  0.726 sq m

(7.8 sq ft)

830 kg

(1828 lb)

based on cabinet footprint:

1143 kg/sq m (234 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

564 kg/sq m (115 lb/sq ft)

16.2 kg/sq cm

(230 lb/sq in.)

InfiniBand switch cabinet 108-port maximum configuration:
  • two 108-Port InfiniBand switches
  • two TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

500 kg (1100 lb)

based on cabinet footprint:

688 kg/sq m (141 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

340 kg/sq m (69 lb/sq ft)

9.5 kg/sq cm

(134 lb/sq in.)

InfiniBand switch cabinet 162-port maximum configuration:
  • one 162-Port InfiniBand switch
  • three TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

396 kg

(872 lb)

based on cabinet footprint:

545 kg/sq m (112 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

269 kg/sq m (55 lb/sq ft)

7.75 kg/sq cm

(109 lb/sq in.)

  0.73 sq m

(7.8 sq ft)

420 kg

(926 lb)

based on cabinet footprint:

578 kg/sq m (119 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

285 kg/sq m (58 lb/sq ft)

8.2 kg/sq cm

(116 lb/sq in.)

Cables   Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system.
Weight and floor loading for Platform Framework Cabinets must be based on the maximum configurations supported by the platform. See the Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.