Environmental Requirements - BAR Managed Servers

Teradata Managed Server for Cabinet and Server Models 4X5, 4X7, and 6X7 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
March 2018
Language
English (United States)
Last Update
2018-05-04
dita:mapPath
tem1471887550369.ditamap
dita:ditavalPath
9211.ditaval.ditaval
dita:id
nue1471650680644
Product Category
Hardware
Environmental Requirement Operational Storage Transit

(Up to 1 Week)

Temperature (dry bulb) a

Allowable b: 15° to 32°C (59° to 90°F)

Recommended c: 18° to 27°C (64.8° to 80.6°F)

5° to 45°C

(41° to 113°F)

-40° to 60°C

(-40° to 140°F)

Moisture

Allowable:

20% to 80% (Relative humidity non-condensing)

Recommended c:

Low end moisture: 5.5°C DP (41.9°F DP)

High end moisture: 60% RH and 15°C DP (59°F DP)

8% to 80%

non-condensing

5% to 95%
Maximum dew point 17°C (62°F) 27°C (80°F) N/A
Maximum altitude b 3050 m (10,000 ft) N/A N/A
Vibration limit

Operational vibration depends on the type of chassis in the cabinet. The operational vibration limit for a typical node is 0.26G (rms) at 10-500 Hz. The operational vibration limit for a typical disk chassis is 0.28G (rms) at 5-500 Hz.

N/A N/A
Static discharge limit 4000 V direct discharge, 8000 V air discharge N/A N/A

a Operating temperature and moisture level is measured at individual chassis inlet.

b Due to lower air density at higher altitudes, the maximum dry bulb operating temperature is derated linearly by a value of 3.3° C per 1000 m (1.8° F per 1000 ft) between the altitude of 900 m (2952 ft) and 3050 m (10,000 ft).

c The allowable environmental envelope is a statement of functionality of the equipment. The recommended environmental envelope is a statement of reliability—operating equipment near the allowable limits for long periods of time could result in increased reliability issues.