42-U Cabinet Specifications | Teradata Vantage - 42-U Cabinet - IntelliFlex Platforms - Teradata Vantage

Preparing Your Site For Teradata Vantageā„¢ Hardware - 1.4

Deployment
VantageCore
Edition
IntelliFlex
Product
IntelliFlex Platforms
Teradata Vantage
Release Number
1.4
Published
October 2022
ft:locale
en-US
ft:lastEdition
2024-01-26
dita:mapPath
bjz1663242053526.ditamap
dita:ditavalPath
oqt1542232706976.ditaval
dita:id
gpk1556809249221
Product Category
Hardware
Teradata Vantage
  • Hinged, vented, and locking front and rear doors
  • Removable side panels (removed on side-by-side cabinet configurations)
  • Front side (left and right) stabilizers for single, standalone cabinets (required)
  • Side cutouts at the rear of the cabinet for inter-cabinet cabling
  • EIA rails labeled with U space numbers, 1 to 42, from bottom to top.

External dimensions of a 42-U cabinet
Feature Height Width Depth
Cabinet frame 204.5 cm (80.5 in.) 61 cm (24 in.) 119.4 cm (47 in.)
+ side stabilizers + 0 + 35.5 cm (14 in.) each side + 22.9 cm (9 in.)
+ front door + 0 + 0 + 5 cm (2 in.)
+ side panels + 0 + 0.4 cm (0.15 in.) + 0
Interior 42U [1U = 4.45 cm (1.75 in.)]; 186.7 cm (73.5 in.) 45.1 cm (17.75 in.) 73.8 cm (29.0 in.)

If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).

Recommended ceiling height of 10 feet prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.

Cabinet weight is 172.4 kg (380 lb) unpopulated; load limit 725.7 kg (1600 lb).


Dimensions of a 42-U cabinet showing front and side views and cabling cutouts