High CPU Configuration |
Estimated power is not expected to exceed 16.4 kW when AC is provided to all power cords with:- Fourteen nodes. Combination of 2x6 nodes, 2 hot standby nodes (HSNs)
- Two solid state storage arrays (SSDs). Each array has a storage controller tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
- Mellanox SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
- Additional TMS/Channel/SAS Worker
|
High I/O Configuration |
Estimated power is not expected to exceed 15.5 kW when AC is provided to all power cords with:- Eleven nodes. Combination of 10 nodes plus 1 hot standby node (HSN)
- Five solid state storage arrays. Each array has a storage tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
- Mellanox SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
Balanced Configuration |
Estimated power is not expected to exceed 16.4 kW when AC is provided to all power cords with:- Thirteen nodes. Combination of 12 nodes plus 1 hot standby node (HSN)
- Three solid state storage arrays. Each array has a storage tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
- SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
- Additional TMS/Channel/SAS Worker
|
Hybrid SSD Configuration (10-node Clique)
|
Estimated power is not expected to exceed 12.1 kW when AC is provided to all power cords with:- A 10-node clique (10 Analytics Database nodes with 768 GB memory)
- One HSN
- Five SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
- Five SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
Hybrid SSD Configuration (12-node Clique)
|
Estimated power is not expected to exceed 12.6 kW when AC is provided to all power cords with:- A 12-node clique (12 Analytics Database nodes with 768 GB memory)
- One HSN
- Four SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
- Four SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
RI-only Configuration (10-node Clique)
|
Estimated power is not expected to exceed 10.2 kW when AC is provided to all power cords with:- A 10-node clique (10 Analytics Database nodes with 768 GB memory)
- One HSN
- Five SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
RI-only Configuration (14-node Clique)
|
Estimated power is not expected to exceed 13.6 kW when AC is provided to all power cords with:- A 14-node clique (14 Analytics Database nodes with 768 GB memory)
- One HSN
- Seven SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
WI-only Configuration (Five SSDs)
|
Estimated power is not expected to exceed 10.0 kW when AC is provided to all power cords with:- A 10-node clique (10 Analytics Database nodes with 768 GB memory)
- One HSN
- Five SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|
WI-only Configuration (Ten SSDs)
|
Estimated power is not expected to exceed 11.9 kW when AC is provided to all power cords with:- A 10-node clique (10 Analytics Database nodes with 768 GB memory)
- One HSN
- Ten SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
- Mellanox SB7800 BYNET switch and one of the following Server Management switches:
- Dell X1052
- Dell N1148T-ON
- Dell N1548
- Ruckus ICX 7150-48
- Two VMSs
- KMM
|