Estimated Power | IntelliFlex 2.x Cabinets - Estimated Power: IntelliFlex 2.x Cabinets - IntelliFlex Platforms - Teradata Vantage

Preparing Your Site For Teradata Vantageā„¢ Hardware - 2.5

Deployment
VantageCore
Edition
IntelliFlex
Product
IntelliFlex Platforms
Teradata Vantage
Release Number
2.5
Published
March 2024
ft:locale
en-US
ft:lastEdition
2024-04-26
dita:mapPath
ske1710762973120.ditamap
dita:ditavalPath
oqt1542232706976.ditaval
dita:id
gpk1556809249221
Product Category
Hardware
Teradata Vantage
High CPU Configuration Estimated power is not expected to exceed 16.4 kW when AC is provided to all power cords with:
  • Fourteen nodes. Combination of 2x6 nodes, 2 hot standby nodes (HSNs)
  • Two solid state storage arrays (SSDs). Each array has a storage controller tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
  • Mellanox SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
  • Additional TMS/Channel/SAS Worker
High I/O Configuration Estimated power is not expected to exceed 15.5 kW when AC is provided to all power cords with:
  • Eleven nodes. Combination of 10 nodes plus 1 hot standby node (HSN)
  • Five solid state storage arrays. Each array has a storage tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
  • Mellanox SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
Balanced Configuration Estimated power is not expected to exceed 16.4 kW when AC is provided to all power cords with:
  • Thirteen nodes. Combination of 12 nodes plus 1 hot standby node (HSN)
  • Three solid state storage arrays. Each array has a storage tray (SSDs) and a dependent tray (SSDs), using DE224C drive enclosures
  • SB7800 or QM8700 BYNET switches and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
  • Additional TMS/Channel/SAS Worker
Hybrid SSD Configuration

(10-node Clique)

Estimated power is not expected to exceed 12.1 kW when AC is provided to all power cords with:
  • A 10-node clique (10 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Five SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
  • Five SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
Hybrid SSD Configuration

(12-node Clique)

Estimated power is not expected to exceed 12.6 kW when AC is provided to all power cords with:
  • A 12-node clique (12 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Four SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
  • Four SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
RI-only Configuration

(10-node Clique)

Estimated power is not expected to exceed 10.2 kW when AC is provided to all power cords with:
  • A 10-node clique (10 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Five SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
RI-only Configuration

(14-node Clique)

Estimated power is not expected to exceed 13.6 kW when AC is provided to all power cords with:
  • A 14-node clique (14 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Seven SSDs using DE224C drive enclosures and 2806 controllers (RI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
WI-only Configuration

(Five SSDs)

Estimated power is not expected to exceed 10.0 kW when AC is provided to all power cords with:
  • A 10-node clique (10 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Five SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs
  • KMM
WI-only Configuration

(Ten SSDs)

Estimated power is not expected to exceed 11.9 kW when AC is provided to all power cords with:
  • A 10-node clique (10 Analytics Database nodes with 768 GB memory)
  • One HSN
  • Ten SSDs using 5350 drive enclosures and 5600 controllers, or DE224C drive enclosures and 5700 controllers (WI arrays)
  • Mellanox SB7800 BYNET switch and one of the following Server Management switches:
    • Dell X1052
    • Dell N1148T-ON
    • Dell N1548
    • Ruckus ICX 7150-48
  • Two VMSs