System Thermal Report - Data Warehouse Appliances

2750 Platform Product and Site Preparation Guide

Product
Data Warehouse Appliances
Published
March 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
epb1471886869774.ditamap
dita:ditavalPath
2750.ditaval.ditaval
dita:id
flv1471648428019
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
2750 Config b 29,100 1,110 0.524 1678 761 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET cabinet with 162-Port InfiniBand Switch and TMSs 13,700 520 0.245 872 396 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b 2750 configuration = 2750 with two 4-node cliques, one virtualized management server (VMS), and server management switches.