42-U Cabinet Footprint and Clearances - Appliance for SAS High-Performance Analytics

Model 720 Platform Product and Site Preparation Guide

Product
Appliance for SAS High-Performance Analytics
Published
March 2018
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
icg1471885722524.ditamap
dita:ditavalPath
720.ditaval.ditaval
dita:id
lga1471649528077
Product Category
Hardware
The required installation and servicing clearances are based on the following:
  • Space needed in front of the cabinet to service an extended chassis
  • Space needed to open and close cabinet doors
  • Space needed between, in front of, and on the sides of the cabinets to install stabilizer feet
If two stand-alone cabinets are placed side-by-side, allow 36 cm (14.5 in.) between cabinets to install the side stabilizer feet. There should be at least 1.3 cm (0.5 in.) between the installed side stabilizer feet.
The minimum aisle width requirements from a technical perspective only are:
  • 101.6 cm (40 in.) front service clearance
  • 81.3 cm (32 in.) rear service clearance

At all levels of government (such as city, state and federal), there are laws that govern minimum aisle width (such as building safety codes, occupational safety regulations, and disability access laws). It is the customer’s responsibility to determine and comply with all applicable laws.

The footprints are shown on data center tiles. Each square represents one tile with a dimension of 61 cm x 61 cm (24 in. x 24 in.).

Footprint and Minimum Clearances for One Cabinet

Footprint and Minimum Clearances for Four Ganged Cabinets

Actual cabinet width is 60.96 cm (24 in.) without side panels. To ensure exact alignment for ganged cabinets, use the exact width when drawing up floor plans and cutting floor tiles.