Once the system is in production, take temperature and humidity measurements for each cabinet to make sure environmental requirements are met.

Even if all preinstallation requirements are met, it is still possible that hot spots exist in a data center. If rearrangement of the cabinets at this point is not feasible, switch out existing vented tiles with vented tiles that have a higher opening percentage.