Site Floor and Ceiling Height Specifications - Active Enterprise Data Warehouse

6800 Platform Product and Site Preparation Guide

Product
Active Enterprise Data Warehouse
Published
February 2018
Language
English (United States)
Last Update
2018-04-19
dita:mapPath
vyt1471885165825.ditamap
dita:ditavalPath
6800.ditaval.ditaval
dita:id
jso1471649458844
Product Category
Hardware
Site Feature Recommended Minimum Height Explanation
Raised floor 61.0 cm (24 in.) If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).
Ceiling 3 m (10 ft) Recommended height prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.