System Thermal Report - Active Enterprise Data Warehouse

6800 Platform Product and Site Preparation Guide

Product
Active Enterprise Data Warehouse
Published
February 2018
Language
English (United States)
Last Update
2018-04-19
dita:mapPath
vyt1471885165825.ditamap
dita:ditavalPath
6800.ditaval.ditaval
dita:id
jso1471649458844
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
6800 Max Config b 25,600 848 0.40 1800 815 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
BYNET Cabinet with 648-Port InfiniBand Switch
  • 26,000
  • 32,500 Max
  • 990
  • 1240 Max
  • 0.467
  • 0.585 Max
1242 563 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b6800 max. configuration: 3+1 6800 with 3 processing nodes, one hot standby node, 4 disk arrays, and switches.