Dual AC Concept - BAR Managed Servers - IntelliBase Platforms - IntelliFlex Platforms

Teradata® Hardware Site Preparation Guide

Product
BAR Managed Servers
IntelliBase Platforms
IntelliFlex Platforms
Published
October 2020
Language
English (United States)
Last Update
2020-10-26
dita:mapPath
fsf1526587780889.ditamap
dita:ditavalPath
exclude_all_interim_filters_FLUTO.ditaval.ditaval
dita:id
fsf1526587780889
Product Category
Hardware

Systems are referred to as dual AC system because the power subsystem in each cabinet can accommodate power from two separate power sources.

Each processing and storage cabinet has either two AC feeder boxes (one on each side of the cabinet), or four AC feeder boxes (two on each side of the cabinet).
  • The AC feeder boxes on one side of the cabinet must be connected to one power source, and the AC feeder boxes on the other side of the cabinet must be connected to a separate power source.
  • By default:
    • If a cabinet has two AC feeder boxes, both share current.
    • If a cabinet has four AC feeder boxes, the top two AC feeder boxes share current, and the bottom two AC feeder boxes share current.
  • If the power source connected to the AC feeder boxes on one side of the cabinet is lost, the current on the AC feeder boxes connected to the remaining power source will increase to take over power for the lost source; however, the system will experience some operational degradation.

Note that power connections to some Ethernet switches are not redundant. A system that loses operation on some of its power cords will lose operation on Ethernet switches that are connected to a single power supply.