Site Floor and Ceiling Height Specifications - Data Warehouse Appliances

2800 Platform Product and Site Preparation Guide

Product
Data Warehouse Appliances
Published
February 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
poq1471900215546.ditamap
dita:ditavalPath
2800.ditaval.ditaval
dita:id
xwb1471648609633
Product Category
Hardware
Site Feature Recommended Minimum Height Explanation
Raised floor 61.0 cm (24 in.) If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).
Ceiling 3 m (10 ft) Recommended height prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.