Unit | Actual Footprint Area (No Stabilizers) | Approx. Installed Weight | Distributed Floor Loading | Concentrated Floor Loading | |
---|---|---|---|---|---|
2800 base
cabinet with three 4+0 cliques (maximum configuration):
|
0.726 sq m (7.8 sq ft) |
968 kg (2134 lb) |
based on cabinet footprint: 1333 kg/sq m (273 lb/sq ft) based on footprint plus servicing clearance required to open doors: 658 kg/sq m (135 lb/sq ft) |
16.8 kg/sq cm (246 lb/sq in.) |
|
BYNET
cabinet 108-port maximum
configuration:
|
0.73 sq m (7.8 sq ft) |
500 kg (1100 lb) |
based on cabinet footprint: 688 kg/sq m (141 lb/sq ft) based on footprint plus servicing clearance required to open doors: 340 kg/sq m (69 lb/sq ft) |
9.5 kg/sq cm (134 lb/sq in.) |
|
0.73 sq m (7.8 sq ft) |
420 kg (926 lb) |
based on cabinet footprint: 578 kg/sq m (119 lb/sq ft) based on footprint plus servicing clearance required to open doors: 285 kg/sq m (58 lb/sq ft) |
8.2 kg/sq cm (116 lb/sq in.) |
||
Cables | Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system. |
The following table shows weight and floor loading for fully loaded
2800
cabinet. Failure to follow
the procedures in Installation Weight Considerations for 2800 Cabinets may result in physical damage and/or bodily
injury.
Vented floor tiles cannot support as much weight as solid tiles. When
moving cabinets in a computer room, replace vented floor tiles with solid floor
tiles along the path where cabinets will be rolled. Failure to do so may cause
damage or collapse of vented floor tiles, resulting in physical damage and/or bodily
injury.
Weight and floor loading for Platform Framework Cabinets must be based
on the maximum configurations supported by the platform. See the
Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.