Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
TMS cabinet 0.68 sq m

(7.33 sq ft)

569 kg

(1254 lb)

based on cabinet footprint:

836 kg/sq m (171 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

400 kg/sq m (81 lb/sq ft)

12.2 kg/sq cm

(159 lb/sq in.)

Cables Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system.