Input Power Plugs and Receptacles - BAR Managed Servers

Teradata Managed Server for Cabinet and Server Models 4X5, 4X7, and 6X7 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
March 2018
ft:locale
en-US
ft:lastEdition
2018-05-04
dita:mapPath
tem1471887550369.ditamap
dita:ditavalPath
9211.ditaval.ditaval
dita:id
nue1471650680644
Product Category
Hardware
Power Plugs/Receptacles for Canada, Colombia, El Salvador, Japan, Mexico, Nicaragua, Panama, South Korea, Taiwan, United States, and Venezuela
Unit Power Plug

(Supplied w/ Component)

Power Receptacle

(Provided by Site)

Nameplate Rating a b

TMS Cabinet

30A NEMA L6-30P

three-wire AC Box

NEMA L6-30P

2 cords per AC box

4 cords per cabinet

NEMA L6-30R

4 receptacles per cabinet

each AC box on separate power source connection: line to line

one site circuit breaker required for each power cord receptacle; customer must provide required site circuit breakers

expected power source: 3-phase Wye with a line to neutral voltage typically 120V or 127V and a line to line voltage of 200V to 240V; this product does not connect to the neutral

alternate expected power source: delta power source 200V to 240V on each side

24A

200-240 V~

a Do not use this table to determine power consumption or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification. For North America, code requires the nameplate current rating to be less than the plug rating.

b Frequency rating is 50 or 60 Hz for all products.

Power Plugs/Receptacles for Most Countries Other Than Canada, Colombia, El Salvador, Japan, Mexico, Nicaragua, Panama, South Korea, Taiwan, United States, and Venezuela *
Unit Power Plug

(Supplied w/ Component)

Power Receptacle

(Provided by Site)

Nameplate Rating a b

TMS Cabinet

32A IEC

Single-Phase Three-Wire

IEC 60309 CEE17, pin and sleeve, 32A, Blue, P+N+E, IP44 Splash proof plug, 1 cord per AC box

2 cords per cabinet

IEC 60309 CEE17, pin and sleeve, 32A, Blue, P+N+E with 6-hour keying

2 receptacles per cabinet

one site circuit breaker required for each power cord receptacle; customer must provide required site circuit breakers

each AC box on separate power source connection: line to neutral

expected power source: 3-phase Wye with a line to neutral voltage of 200V to 240V; only one phase per plug used by this product

32A

220-240 V~

a Do not use this table to determine power consumption, to estimate current draw, or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification.

b Frequency rating is 50 or 60 Hz for all products.

* Bahrain, Brazil, Lebanon, Philippines, and Saudi Arabia require discussions with the site team to determine the appropriate power feature for the specific site.