42-U Cabinet Footprint and Clearances - BAR Managed Servers

Teradata Platform Framework Cabinet Model 12 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
February 2018
Language
English (United States)
Last Update
2018-04-18
dita:mapPath
lur1471887722020.ditamap
dita:ditavalPath
9212.ditaval.ditaval
dita:id
tlu1471650703436
Product Category
Hardware
The required installation and servicing clearances are based on the following:
  • Space needed in front of the cabinet to service an extended chassis
  • Space needed to open and close cabinet doors
  • Space needed between, in front of, and on the sides of the cabinets to install stabilizer feet
If two stand-alone cabinets are placed side-by-side, allow 36 cm (14.5 in.) between cabinets to install the side stabilizer feet. There should be at least 1.3 cm (0.5 in.) between the installed side stabilizer feet.
The minimum aisle width requirements from a technical perspective only are:
  • 101.6 cm (40 in.) front service clearance
  • 81.3 cm (32 in.) rear service clearance

At all levels of government (such as city, state and federal), there are laws that govern minimum aisle width (such as building safety codes, occupational safety regulations, and disability access laws). It is the customer’s responsibility to determine and comply with all applicable laws.

The footprints are shown on data center tiles. Each square represents one tile with a dimension of 61 cm x 61 cm (24 in. x 24 in.).

Footprint and Minimum Clearances for One Cabinet

Footprint and Minimum Clearances for Four Ganged Cabinets

Actual cabinet width is 60.96 cm (24 in.) without side panels. To ensure exact alignment for ganged cabinets, use the exact width when drawing up floor plans and cutting floor tiles.