Site Floor and Ceiling Height Specifications - BAR Managed Servers

Teradata Platform Framework Cabinet Model 12 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
February 2018
Language
English (United States)
Last Update
2018-04-18
dita:mapPath
lur1471887722020.ditamap
dita:ditavalPath
9212.ditaval.ditaval
dita:id
tlu1471650703436
Product Category
Hardware
Site Feature Recommended Minimum Height Explanation
Raised floor 61.0 cm (24 in.) If a raised floor is used as a cold air delivery plenum, Teradata recommends that the raised floor height be greater than 61 cm (24 in.).
Ceiling 3 m (10 ft) Recommended height prevents warm air that is exhausted at the rear of the cabinets from being trapped in the area above the cabinets, and from being recirculated back into the inlets of the hardware equipment.