Weight and Floor Loading - BAR Managed Servers

Teradata Platform Framework Cabinet Model 12 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
February 2018
Language
English (United States)
Last Update
2018-04-18
dita:mapPath
lur1471887722020.ditamap
dita:ditavalPath
9212.ditaval.ditaval
dita:id
tlu1471650703436
Product Category
Hardware
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
Platform Framework Cabinet   0.73 sq m

7.8 sq ft

624 kg

1375 lb

based on cabinet footprint:

859 kg/sq m (176 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

424 kg/sq m (87 lb/sq ft)

12.2 kg/sq cm

(173 lb/sq in.)

Cables   Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system.