Platform Framework Cabinet Four-Cord 30A/32A Splash-Proof Power Plugs and Receptacles
The following plug type is for worldwide use. It is used phase-to-phase in locations with traditional North American power and single phase (line-to-neutral) in locations with traditional European power.
Unit |
PFC Cabinet |
Power Type |
30A/32A phase-phase or single phase power |
Nameplate Rating a b |
|
Expected Utility Power Sources (Provided by Site) |
Or
|
Power Plug and Number of Cords (Supplied with Product) |
IEC 60309 CEE17, pin and sleeve, 30/32A, Blue (250V), 2P3W, with 6-hour keying, IP44 splash-proof plug (Walther Electric brand is shown below. Actual brand supplied with cabinet may vary.) Four AC box cords per cabinet, top or bottom egress. The minimum bend radius limit for
the power cord is 12.8 cm (5.0 in.). Do not bend the power cord
tighter than this limit.
|
AC Box Power Cord Connections to Site Power (For Redundancy) |
The two power cords on the orange AC box in the cabinet connect to one site power source. The two power cords on the blue AC box in the cabinet connect to the second site power source. |
Power Receptacle or Connector and Circuit Breakers (Provided by Site) |
IEC 60309 CEE17, pin and sleeve, 30/32A, Blue (250V), 2P3W, with 6-hour keying, IP44 splash-proof receptacle or connector Example receptacles
(similar products are available from other companies):
Example connectors for use with cordage (similar
products are available from other companies):
Example connectors for use with
¾-inch NPT fitting for connection to conduit: c
Customer to supply four receptacles or connectors per cabinet. d One site circuit breaker required for each power cord; customer must provide required site circuit breakers. Each AC box on separate power source connection. |
a Do not use this table to determine power consumption, to estimate current draw, or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification. b Frequency rating is 50 or 60 Hz for all products. c Conduit Adapters do not connect to the ground terminal of the connector. Consult your local code grounding requirements before using adapters. d Obtain connectors by ordering kit 2021-K900. Two kits are required per Platform Framework Cabinet. |