Universal builds for IntelliFlex 2.1.1 or 2.5 High CPU configurations contain mixed use arrays using DE224C drive enclosures, and may contain single or multiple cliques. Each IntelliFlex High CPU cabinet may include any of the following, depending on the customer's system configuration and cabinet power type.
- Up to seven Analytics Database nodes for Power A; up to 14 nodes for Power BCD.
- Analytics Database
- One mixed use array for Power A; up to two mixed use arrays for Power BCD.
- One PE or TMS/Channel/SWS Worker node may be added for Power A.
- Two VMS 3.0 or VMS 4.0 (required).
- One rackmount KMM.
- Two 36-port EDR first-tier InfiniBand switches (optional in expansion cabinets).
- Two 36-port EDR second-tier InfiniBand switches (optional in expansion cabinets).
- Two 1 GB Ethernet switches
- Two 10 GB CLAN switches (optional)
- Up to three 2U Servers (TMS, Channel Server, or SWS) for Power A; up to four 2U Servers (TMS, Channel Server, or SWS) for Power BCD.
For more information on the customer's system configuration, contact the Teradata account team.
Build Rules
Components must be installed in a certain order as indicated in the build graphics, with maximum numbers of each limited by the power type used in the system.
- Install RBOD (Controller) and EBOD (IOM) arrays (using DE224C drive enclosure) from the bottom of the cabinet up, in the following order:
Power Type BCD Power Type A RBOD in U spaces 2-3 ● ● EBOD (IOM) in U spaces 4-5 ● ● RBOD in U spaces 6-7 ● ● EBOD (IOM) in U spaces 8-9 ● ● - After installing the storage arrays, install nodes (starting with Analytics Database nodes, then Analytics Nodes, and then PE nodes) from the bottom of the cabinet up in the following order:
Power Type BCD Power Type A Chassis in U space 10 ● Chassis in U spaces 14-15 ● Chassis in U spaces 16-19 ● ● Chassis in U spaces 25-29 ● ● Chassis in U spaces 30-31 ● Chassis in U space 33 ● Chassis in U space 37 ● - Install TMS, Channel, and SAS Worker nodes, in the following order:
Power Type BCD Power Type A Chassis in U spaces 14-15 ● Chassis in U spaces 25-30 ● ● Chassis in U spaces 33-34 ● Chassis in U spaces 37-38 ● - Install all remaining components from the bottom of the cabinet up, for all power types, in the following order:
Primary Server Management Switch, 48 Port 1 GbE U space 1, fixed VMS 3.0 or VMS 4.0 (R1208WF) U space 20 and 23, if present KMM (optional) U space 21, if present InfiniBand Switch, 36-port EDR, first-tier (optional in expansion cabinets) U spaces 22 and 24, if present InfiniBand Switch, 36-port EDR, second-tier (optional in expansion cabinets) U spaces 20 and 21, if present 10 GB Ethernet Switch (optional) Field Install only
U spaces 41 and 42, if present Secondary Server Management Switch, 48 Port 1 GbE Attic space, fixed
Example Builds: IntelliFlex 2.1.1 or 2.5 High CPU Configuration
The build graphics for High CPU configurations show standard configuration blocks on the left side of the image. Columns on the right show allowed positions for systems using a combination of 1U nodes and 2U node/server chassis, including TMSs, channel servers, and SWS worker nodes.
Placement of chassis must follow the install build rules without exception to adhere to power constraints for the respective power types.
Type BCD Power
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5
IntelliFlex 2.1.1 or 2.5