IntelliFlex 2.x Cabinet Build System Expansion Analytics Nodes | Vantage - Universal Cabinets: IntelliFlex Release 2.x (System Expansion with Analytics Nodes) - BAR Managed Servers - IntelliFlex Platforms - Teradata Vantage

Teradata Vantage™ Hardware Cabinet Build Reference - 1.4

Product
BAR Managed Servers
IntelliFlex Platforms
Teradata Vantage
Release Number
1.4
Published
October 2022
Language
English (United States)
Last Update
2022-11-21
dita:mapPath
elg1663242132070.ditamap
dita:ditavalPath
zjj1603403324805.ditaval
dita:id
B035-6213
Product Category
Hardware
Teradata Vantage
Starting with Vantage release 1.1.1, existing IntelliFlex Hybrid (Release 2.0 and 2.1), Read Intensive (Release 2.0 only), and 2.1.1 (High CPU only) systems may be expanded to include Analytics Nodes.
Each cabinet may include the following, depending on the customer's system configuration and cabinet power types:
  • Up to eight Analytics Nodes
  • Up to two mixed-use arrays
  • Two VMSs
  • One rackmount KMM (optional)
  • Two 36-port EDR first-tier InfiniBand switches (optional in expansion cabinets)
  • Two 36-port EDR second-tier InfiniBand switches (optional in expansion cabinets)
  • Two 1 GB Ethernet switches (allowed only as shown in the following build graphics)
  • Two 10 GB CLAN switches (optional)
  • Up to two TMS or PE nodes (allowed only as shown in the following build graphics)

For more information on the customer's system configuration, please contact the Teradata account team.

Build Rules for IntelliFlex 2.x Expansions with Analytics Nodes

Components must be installed in a certain order, with maximum numbers of each limited by the power type used in the system.

  1. Install RBOD (Controller) and EBOD (IOM) arrays (using DE224C drive enclosure) from the bottom of the cabinet up, in the following order as indicated in the following diagrams:
      Power Type BCD Power Type A
    RBOD in U spaces 2-3 n/a
    EBOD (IOM) in U spaces 4-5
    RBOD in U spaces 6-7
    EBOD (IOM) in U spaces 8-9
  2. After installing the storage arrays, install nodes (starting with Analytics Database nodes, then Analytics Nodes, and then PE nodes) from the bottom of the cabinet up, in the following order as indicated in the following diagrams:
      Power Type BCD Power Type A
    Chassis in U space 10  
    Chassis in U spaces 14-19
    Chassis in U spaces 25-27
    Chassis in U space 28  
    Chassis in U space 29
    Chassis in U spaces 30-31  
    Chassis in U space 33  
    Chassis in U space 37    
  3. Install TMS, Channel, and SAS Worker nodes, in the following order:
      Power Type BCD Power Type A
    Chassis in U spaces 27-30  
    Chassis in U spaces 31-34  
  4. Install all remaining components from the bottom of the cabinet up, for all power types, in the following order:
    Primary Server Management Switch, 48 Port 1 GbE U space 1, fixed
    VMS 3.0 (R1208WF) U spaces 20 and 23
    KMM (optional) U space 21, if present
    InfiniBand Switch, 36-port EDR, second-tier (optional in expansion cabinets) U spaces 20 and 21
    InfiniBand Switch, 36-port EDR, first-tier (optional in expansion cabinets) U spaces 22 and 24
    10 GB Ethernet Switch (optional)

    Field Install only

    U spaces 41 and 42
    Secondary Server Management Switch, 48 Port 1 GbE Attic space, fixed

Example Builds: IntelliFlex 2.x System Expansion with Analytics Nodes

IntelliFlex 2.x build graphics show standard configuration blocks on the left side of the image. Columns on the right show allowed positions for systems using a combination of 1U nodes and 2U node/server chassis.

Placement of chassis must follow the install build rules without exception to adhere to power constraints for the respective power types.

IntelliFlex 2.0 or 2.1 Example cabinet build for IntelliFlex 2.x system expansion: (6+1) + 8 Analytics Nodes + extra node with type BCD power
IntelliFlex 2.0 or 2.1 Example cabinet build for IntelliFlex 2.x system expansion: (6+1) + 8 Analytics Nodes + TMS with type BCD power
IntelliFlex 2.1.1 or 2.5