Cabinet builds for 9400 cabinet configurations use build rules to define a valid system configuration. Cabinets can contain single or multiple cliques or systems.

Build Rules

Install components in sequential order per the rules below, with maximum numbers of each limited by the power type used in the cabinet.

The maximum number of switches (not including server management switches) is four, except in the BYNET cabinet configuration, which can have up to eight second-tier BYNET switches in addition to two first-tier BYNET switches.

Two Dell X1026, Dell X1052, or Dell N1148T-ON 1 Gb Ethernet switches are installed per cabinet, in the attic and U-space 1, for Server Management in all 9400 cabinet builds.

General Purpose Cabinets

Chassis Procedure
For the following:
  • KMM
  • VMS
  • BYNET switches
  • Lenovo switch
See cabinet configurations for installation location.

4+0 or 2+0 cliques must be installed in the lower-half cabinet at factory. The 4+0 or 2+0 cliques at top-half cabinet are Field Install Only.

For the following:
  • Ancillary servers
  • TMS
  • 1 GbE switch
  • 10 GbE switch
  • Brocade switch
Install from the bottom up in this order:
  1. Ancillary servers
  2. TMS
  3. Switches
VMS
  • VMS 3.0 (R1208WF), or VMS 2.0 System VMS (R1208WT): U18
  • VMS 3.0 (R1208WF), or VMS 2.0 Cabinet VMS (R1208WT): U16

BAR Cabinets: i3 Tape Library (Base and Expansion)

Chassis Location
Space Reservation Feature Note locations in the i3 cabinet builds. Each block of i3 Tape Library (Base and Expansion) must be installed from the bottom up.
SKM U4 and U6
1 GbE switch U2
i3-associated TMS From the bottom up

For TMS above i3, install top-down starting at U40

KMM/ VMS (If ordered and space allows)
  • VMS 3.0 (R1208WF), or VMS 2.0 System VMS (R1208WT): U18
  • VMS 3.0 (R1208WF), or VMS 2.0 Cabinet VMS (R1208WT): U16
  • KMM: U22, or any open space in U19-U23 locations
All other equipment Install bottom-up in the following order:
  1. Ancillary servers
  2. SMP (install storage below the server)
  3. Other TMS
  4. Switches (Dell X1026, Dell X1052, Dell N1148T-ON, Lenovo, Brocade, and BYNET)

BAR Cabinets: DD6800, DD6900, DD9300, DD9400, DS60, ES30

Chassis Location
Space Reservation Feature Install top-down per the DD6800/DD6900 or DD9300/DD9400 cabinet builds
BAR-associated TMS Install bottom-up
KMM / VMS if ordered and space allows
  • VMS 3.0 (R1208WF), or VMS 2.0 System VMS (R1208WT): U18
  • VMS 3.0 (R1208WF), or VMS 2.0 Cabinet VMS (R1208WT): U16
  • KMM: U22 or any open space in U19 through U23
All other equipment Install bottom-up in the following order:
  1. Ancillary servers
  2. SMP (install storage below the server)
  3. Other TMS
  4. Switches (Dell X1026, Dell X1052, Dell N1148T-ON, Lenovo, Brocade, and BYNET)

BYNET Cabinet

Chassis Location
BYNET switch (pair) Install according to BYNET cabinet configurations
KMM or VMS Install according to BYNET cabinet configurations
TMS Bottom-up, per the BYNET cabinet configurations (see Server Fill below)
Second-tier switches (bottom egress)
  1. First pair: U23 and U25
  2. Second pair: U16 and U18
  3. Third pair: U2 and U4
  4. Fourth pair: U6 and U8
Second-tier switches (top egress)
  1. First pair: U23 and U25
  2. Second pair: U16 and U18
  3. Third pair: U37 and U39
  4. Fourth pair: U33 and U35

Server Fill

A 9400 cabinet can contain a variety of chassis that do not fit in the processing/storage cabinet.

Chassis Location
Servers Install bottom-up, using the following order:
  1. Install Hadoop clusters in ascending order:
    1. Appliance 6 master
    2. Data node
    3. Appliance 6 edge node
  2. Install Consolidated TMS by feature in ascending order.
  3. Install SAS worker node.
  4. Install channel server.