Evaluating Temperature and Humidity | Teradata Vantage - Evaluating Temperature and Humidity - IntelliFlex Platforms - Teradata Vantage

Preparing Your Site For Teradata Vantageā„¢ Hardware

Product
IntelliFlex Platforms
Teradata Vantage
Release Number
1.0
Published
May 2019
Language
English (United States)
Last Update
2022-09-22
dita:mapPath
iin1558129751076.ditamap
dita:ditavalPath
ft:empty
dita:id
B035-6210
lifecycle
previous
Product Category
Hardware
Teradata Vantage

Once the system is in production, take temperature and humidity measurements for each cabinet to make sure environmental requirements are met.

Even if all preinstallation requirements are met, it is still possible that hot spots exist in a data center. If rearrangement of the cabinets at this point is not feasible, switch out existing vented tiles with vented tiles that have a higher opening percentage.