Cooling Considerations - Teradata IntelliCloud

Teradata® IntelliCloud™ for On-Premises Customer Hosting Guide

prodname
Teradata IntelliCloud
created_date
October 2019
category
Product Guide
featnum
B035-6111-078K

Two vented tiles per cabinet are required for a single cabinet row. We recommend a minimum distance of 2.4 m (8 ft) – or four floor tiles – in the cold aisles. Perforated floor panels or grills must fill the cold aisles.

Cold Aisle (Vented Tiles) Hot Aisle (Solid Tiles)
Use between two rows of cabinets aligned face-to-face Use between two rows of cabinets aligned rear-to-rear