Replacing a Power Supply/Cooling Module - Data Mart Appliances

670 Platform Hardware Replacement Guide for Customers

Product
Data Mart Appliances
Published
July 2013
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
scd1471886401658.ditamap
dita:ditavalPath
670.ditaval.ditaval
dita:id
noz1471648710034
Product Category
Hardware
Although this is a hot swap component, Teradata requires that you use the FRU replacement procedure in Server Management Client.

Observe all servicing cautions and warnings.

Replacing a power supply/cooling module may require a restart of the Teradata Database . Before starting this procedure, the CSR must communicate to the customer that replacing a power supply/cooling module may require a database restart and, if necessary, coordinate with the customer to find a convenient time for performing the procedure.

These illustrations show the replacement of a power supply in a drive enclosure that contains controller modules. The replacement steps for a power supply in an enclosure with ESMs are identical.
To prevent the storage drives from overheating, replace a failed power supply/cooling module within three minutes of removal. If replacing the module will take longer than three minutes, the Teradata Database must be stopped and the drive enclosure powered down.