System Thermal Report - Integrated Big Data Platforms

1800 Platform Product and Site Preparation Guide

Product
Integrated Big Data Platforms
Published
February 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
jjw1471890141106.ditamap
dita:ditavalPath
1800.ditaval.ditaval
dita:id
vve1471647838623
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
1800 2+1 Config b 24,600 940 0.444 1689 766 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
BYNET Cabinet with 648-Port InfiniBand Switch
  • 26,000
  • 32,500 Max
  • 990
  • 1240 Max
  • 0.467
  • 0.585 Max
1242 563 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b 1800 max configuration = Two TPA nodes, one hot standby node, 15 drive enclosures with 12 drives each, one KVM, one VMS, two BYNET switches, two server management switches, and power hardware.