Input Power Plugs and Receptacles - BAR Managed Servers

Teradata Managed Server for Cabinet and Server Models 4X5, 4X7, and 6X7 Product and Site Preparation Guide

Product
BAR Managed Servers
Published
March 2018
Language
English (United States)
Last Update
2018-05-04
dita:mapPath
tem1471887550369.ditamap
dita:ditavalPath
9211.ditaval.ditaval
dita:id
nue1471650680644
Product Category
Hardware
Power Plugs/Receptacles for Canada, Colombia, El Salvador, Japan, Mexico, Nicaragua, Panama, South Korea, Taiwan, United States, and Venezuela
Unit Power Plug

(Supplied w/ Component)

Power Receptacle

(Provided by Site)

Nameplate Rating a b

TMS Cabinet

30A NEMA L6-30P

three-wire AC Box

NEMA L6-30P

2 cords per AC box

4 cords per cabinet

NEMA L6-30R

4 receptacles per cabinet

each AC box on separate power source connection: line to line

one site circuit breaker required for each power cord receptacle; customer must provide required site circuit breakers

expected power source: 3-phase Wye with a line to neutral voltage typically 120V or 127V and a line to line voltage of 200V to 240V; this product does not connect to the neutral

alternate expected power source: delta power source 200V to 240V on each side

24A

200-240 V~

a Do not use this table to determine power consumption or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification. For North America, code requires the nameplate current rating to be less than the plug rating.

b Frequency rating is 50 or 60 Hz for all products.

Power Plugs/Receptacles for Most Countries Other Than Canada, Colombia, El Salvador, Japan, Mexico, Nicaragua, Panama, South Korea, Taiwan, United States, and Venezuela *
Unit Power Plug

(Supplied w/ Component)

Power Receptacle

(Provided by Site)

Nameplate Rating a b

TMS Cabinet

32A IEC

Single-Phase Three-Wire

IEC 60309 CEE17, pin and sleeve, 32A, Blue, P+N+E, IP44 Splash proof plug, 1 cord per AC box

2 cords per cabinet

IEC 60309 CEE17, pin and sleeve, 32A, Blue, P+N+E with 6-hour keying

2 receptacles per cabinet

one site circuit breaker required for each power cord receptacle; customer must provide required site circuit breakers

each AC box on separate power source connection: line to neutral

expected power source: 3-phase Wye with a line to neutral voltage of 200V to 240V; only one phase per plug used by this product

32A

220-240 V~

a Do not use this table to determine power consumption, to estimate current draw, or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification.

b Frequency rating is 50 or 60 Hz for all products.

* Bahrain, Brazil, Lebanon, Philippines, and Saudi Arabia require discussions with the site team to determine the appropriate power feature for the specific site.