System Thermal Report - Integrated Big Data Platforms

1700 Platform Product and Site Preparation Guide

Product
Integrated Big Data Platforms
Published
March 2018
Language
English (United States)
Last Update
2018-04-17
dita:mapPath
esf1471887251194.ditamap
dita:ditavalPath
1700.ditaval.ditaval
dita:id
ffn1471647521493
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
1700 2 + 1 Config b 18,800 720 0.340 1600 725 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET cabinet with 162-Port InfiniBand Switch and TMSs 13,700 520 0.245 872 396 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b 1700 max configuration = Two TPA nodes, one hot standby node, 15 drive enclosures with 12 drives each, one KVM, one VMS, two BYNET switches, two server management switches, and power hardware.