Hardware Placement Guidelines for Non-Raised Floor and Containment Environment - BAR Managed Servers - IntelliBase Platforms - IntelliFlex Platforms

Teradata® Hardware Site Preparation Guide

Product
BAR Managed Servers
IntelliBase Platforms
IntelliFlex Platforms
Published
October 2020
Language
English (United States)
Last Update
2020-10-26
dita:mapPath
fsf1526587780889.ditamap
dita:ditavalPath
exclude_all_interim_filters_FLUTO.ditaval.ditaval
dita:id
fsf1526587780889
Product Category
Hardware

If a Teradata system is to be installed in a containment environment or a non-raised floor environment, the site team must consult with Teradata. The site team must prepare a detailed site survey and analysis to help determine the proper equipment layouts to meet the stated environmental requirements for the system.

Make sure of the following when designing the floor layout:
Include the following personnel when discussing the layout:
  • Facility personnel at the site, to discuss data center-related issues
  • Teradata regional installation personnel with assistance from Teradata Engineering
Cold Air Delivery through Overhead Diffusers in an Open Environment
Cold air delivery (diffusers) in open environment
Cold Air Delivery through Overhead Diffusers in Cold Aisle Containment Environment
Cold air delivery (diffusers) in cold aisle containment environment
Cold Air Delivery through Vented Tiles in Cold Aisle Containment Environment
Cold air delivery (vented files) in cold aisle containment environment
Cold Air Delivery through Vented Tiles in Hot Aisle Containment Environment
Cold air delivery (vented files) in hot aisle containment environment
Cold Air Delivery through Cabinet Front by In-Row Cooling Units in Hot Aisle Containment Environment
Cold air delivery (cooling units) in hot aisle containment environment