The following table shows weight and floor loading for fully loaded 2800 cabinet. Failure to follow the procedures in Installation Weight Considerations for 2800 Cabinets may result in physical damage and/or bodily injury.
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
2800 base cabinet with three 4+0 cliques (maximum configuration):
  • twelve drive enclosures, six with controllers
  • eight processing nodes
  • one VMS
  • one KVM
  • two 36-port BYNET V5 InfiniBand switches
  • two 24-port server management Ethernet switches
  • four PDU strips
  • four 30 Amp AC feeder boxes
  • doors
  • cabinet
  0.726 sq m

(7.8 sq ft)

968 kg

(2134 lb)

based on cabinet footprint:

1333 kg/sq m (273 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

658 kg/sq m (135 lb/sq ft)

16.8 kg/sq cm

(246 lb/sq in.)

BYNET cabinet 108-port maximum configuration:
  • two 108-Port InfiniBand switches
  • two TMSs
  • one VMS
  • one KVM
  • two 48-port server management Ethernet switches
  • cabinet
  • doors
  0.73 sq m

(7.8 sq ft)

500 kg (1100 lb)

based on cabinet footprint:

688 kg/sq m (141 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

340 kg/sq m (69 lb/sq ft)

9.5 kg/sq cm

(134 lb/sq in.)

  0.73 sq m

(7.8 sq ft)

420 kg

(926 lb)

based on cabinet footprint:

578 kg/sq m (119 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

285 kg/sq m (58 lb/sq ft)

8.2 kg/sq cm

(116 lb/sq in.)

Cables   Allow an additional 22.68 kg (50 lb) per system for the installed weight of the cables. Actual weight will vary depending on the number of cables routed through the cable management system.
Weight and floor loading for Platform Framework Cabinets must be based on the maximum configurations supported by the platform. See the Teradata Platform Framework Cabinet Model 12 Hardware Service Guide, B035-5389.