InfiniBand 162-Port and 324-Port Cabinet Two-Cord 30A/32A Splash-Proof Power Plugs and Receptacles - Appliance for SAS High-Performance Analytics

Model 720 Platform Product and Site Preparation Guide

Product
Appliance for SAS High-Performance Analytics
Published
March 2018
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
icg1471885722524.ditamap
dita:ditavalPath
720.ditaval.ditaval
dita:id
lga1471649528077
Product Category
Hardware

The following plug type is for worldwide use. It is used phase-to-phase in locations with traditional North American power and single phase (line-to-neutral) in locations with traditional European power.

InfiniBand 162-Port and 324-Port Cabinet Two-Cord 30A/32A Splash-Proof Power Plugs and Receptacles

Unit

InfiniBand switch cabinet with 162-Port and 324-Port switches

Power Type

30A/32A phase-phase or single phase power

  • Plug is rated at 30A for North America
  • Plug is rated at 32A for Europe

Nameplate Rating a b

  • 24A per cord
  • 200-240V~

Expected Utility Power Sources

(Provided by Site)

  • 230 V wired line-to-neutral (single-phase) . With this line-to-neutral source, the power plug connects to line, neutral, and safety ground.
    This utility source is typical in Europe, but is now sometimes found in North America in new, specialized data centers.

Or

  • Wired line-to-line (phase-phase)
    This utility source is typically used in North America and Japan.
    • Three-phase Wye with a line-to-neutral voltage typically 120V or 127V and a line to line voltage of 200V to 240V.
    • Alternate expected power source (Japan): Delta power source 200V to 240V on each side.
    With either of the last two utility power sources, each of the 3-pin power plugs connect to two of the three lines and also to safety ground. With these sources the power plug does not connect to neutral.

Power Plug and Number of Cords

(Supplied with Product)

IEC 60309 CEE17, pin and sleeve, 30/32A, Blue (250V), 2P3W, with 6-hour keying, IP44 splash-proof plug

(Walther Electric brand is shown below. Actual brand supplied with cabinet may vary.)

Two AC box cords per cabinet, top or bottom egress.

The minimum bend radius limit for the power cord is 12.8 cm (5.0 in.). Do not bend the power cord tighter than this limit.

AC Box Power Cord Connections to Site Power

(For Redundancy)

The power cord on the orange AC box in the cabinet connects to one site power source. The power cord on the blue AC box in the cabinet connects to the second site power source.

Power Receptacle or Connector

and

Circuit Breakers

(Provided by Site)

IEC 60309 CEE17, pin and sleeve, 30/32A, Blue (250V), 2P3W, with 6-hour keying, IP44 splash-proof receptacle or connector

Example receptacles (similar products are available from other companies):
  • Scame Electrical Solutions SCM330R6S (shown above)
  • Walther Electric 430306

Example connectors for use with cordage (similar products are available from other companies):
  • ABL Sursum K32S20A
  • Scame Electrical Solutions SCM330C6S
  • Walther Electric 330306 (shown above)
  • Walther Electric 331306
Example connector for use with ¾-inch NPT fitting for connection to conduit:
  • Walther Electric PG21-75 combined with Walther Electric 331306

Customer to supply two receptacles or connectors per cabinet. c

One site circuit breaker required for each power cord; customer must provide required site circuit breakers.

Each AC box on separate power source connection.

a Do not use this table to determine power consumption, to estimate current draw, or to estimate heat generation. For these parameters, see Site Environmental Planning. Nameplate ratings are a statement of product certification.

b Frequency rating is 50 or 60 Hz for all products.

c For 162-Port and 324-Port cabinets: Customer can obtain connectors from any source. Connectors are available from Teradata by ordering kit 2021-K900. One kit is required per InfiniBand switch cabinet.