Three-Phase AC Box - Phase Current Balancing - Appliance for SAS High-Performance Analytics

Model 720 Platform Product and Site Preparation Guide

Product
Appliance for SAS High-Performance Analytics
Published
March 2018
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
icg1471885722524.ditamap
dita:ditavalPath
720.ditaval.ditaval
dita:id
lga1471649528077
Product Category
Hardware
Phase currents are not balanced on three-phase AC feeder boxes. If you have more than one cabinet with the three-phase AC feeder box, you will need to rotate the phase connections on each outlet to minimize the aggregate site imbalance. Consult this table for how to connect the phases to the receptacle in order to rotate the phase connections.
With a three-phase Wye AC feeder box, the phase imbalance results in a current on the neutral wire.
Three-Phase AC Box Current Balancing
Cabinet # Phase #1 Phase #2 Phase #3
Cabinet #1 L1 L2 L3
Cabinet #2 L3 L1 L2
Cabinet #3 L2 L3 L1
Cabinet #4 L1 L2 L3
Cabinet #5 L3 L1 L2
Cabinet #6 L2 L3 L1
Cabinet #7 and so on and so on and so on