System Thermal Report - Data Warehouse Appliances

2700 Platform Product and Site Preparation Guide

Product
Data Warehouse Appliances
Published
March 2018
Language
English (United States)
Last Update
2018-04-18
dita:mapPath
yop1471886638949.ditamap
dita:ditavalPath
2700.ditaval.ditaval
dita:id
zqx1471648424914
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
2700 Config 1b 27,300 1,040 0.491 1678 761 See Dimensions: 42-U Cabinet
2700 Config 2c 33,510 1,280 0.604 1678 761 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET cabinet with 162-Port InfiniBand Switch and TMSs 13,700 520 0.245 872 396 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b2700 configuration 1 = Six processing nodes with two CPUs each, ten drive enclosures with twenty-four storage drives each, two TMS servers, one VMS, two BYNET switches, and two server management switches.

c2700 configuration 2 = Four processing nodes with two CPUs each, six drive enclosures with twenty-four storage drives each, eight TMS servers, one VMS, two BYNET switches, and two server management switches.