Cabinet | Typical Heat Dissipation | Air Flow Nominal | Weight | Overall Cabinet Dimensions | ||
---|---|---|---|---|---|---|
BTU/Hr a | CFM | m 3/sec | lb | kg | ||
2700 Config 1b | 27,300 | 1,040 | 0.491 | 1678 | 761 | See Dimensions: 42-U Cabinet |
2700 Config 2c | 33,510 | 1,280 | 0.604 | 1678 | 761 | See Dimensions: 42-U Cabinet |
BYNET cabinet with 108-Port InfiniBand Switch and TMSs | 15,400 | 590 | 0.278 | 1100 | 500 | See Dimensions: 42-U Cabinet |
BYNET cabinet with 162-Port InfiniBand Switch and TMSs | 13,700 | 520 | 0.245 | 872 | 396 | See Dimensions: 42-U Cabinet |
BYNET Cabinet with 324-Port InfiniBand Switch |
|
|
|
926 | 420 | See Dimensions: 42-U Cabinet |
ASHRAE Class 1 |
|
|||||
a 1 watt = 3.412 BTU/Hr. b2700 configuration 1 = Six processing nodes with two CPUs each, ten drive enclosures with twenty-four storage drives each, two TMS servers, one VMS, two BYNET switches, and two server management switches. c2700 configuration 2 = Four processing nodes with two CPUs each, six drive enclosures with twenty-four storage drives each, eight TMS servers, one VMS, two BYNET switches, and two server management switches. |