System Thermal Report - Active Enterprise Data Warehouse

6700 Platform Product and Site Preparation Guide

Product
Active Enterprise Data Warehouse
Published
March 2018
Language
English (United States)
Last Update
2018-04-18
dita:mapPath
npo1471884913832.ditamap
dita:ditavalPath
6700.ditaval.ditaval
dita:id
gka1471649157954
Product Category
Hardware
Cabinet Typical Heat Dissipation Air Flow Nominal Weight Overall Cabinet Dimensions
BTU/Hr a CFM m 3/sec lb kg
6700C/H/X Max Config b 24,300 925 0.436 1760 798 See Dimensions: 42-U Cabinet
BYNET cabinet with 108-Port InfiniBand Switch and TMSs 15,400 590 0.278 1100 500 See Dimensions: 42-U Cabinet
BYNET cabinet with 162-Port InfiniBand Switch and TMSs 13,700 520 0.245 872 396 See Dimensions: 42-U Cabinet
BYNET Cabinet with 324-Port InfiniBand Switch
  • 11,300
  • 15,100 Max
  • 430
  • 580 Max
  • 0.203
  • 0.274 Max
926 420 See Dimensions: 42-U Cabinet
ASHRAE Class 1


 

a 1 watt = 3.412 BTU/Hr.

b6700 max. configuration: 3+1 6700H with 3 processing nodes, one hot standby node, 5 disk arrays, and switches.