Vented floor tiles cannot support as much weight as solid tiles. When
moving cabinets in a computer room, replace vented floor tiles with solid floor
tiles along the path where cabinets will be rolled. Failure to do so may cause
damage or collapse of vented floor tiles, resulting in physical damage and/or bodily
injury.
Unit | Actual Footprint Area (No Stabilizers) | Approx. Installed Weight | Distributed Floor Loading | Concentrated Floor Loading | |
---|---|---|---|---|---|
750 cabinet
maximum configuration:
|
0.726 sq m (7.8 sq ft) |
827 kg (1825 lbs) |
based on cabinet footprint: 1137 kg/sq m (233 lb/sq ft) based on footprint plus servicing clearance required to open doors: 562 kg/sq m (115 lb/sq ft) |
14.06 kg/sq cm (200 lb/sq in.) |