Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
750 cabinet maximum configuration:
  • eighteen SAS HPA Performance Worker nodes
  • one VMS
  • one KVM
  • two InfiniBand switches
  • two 24-port server management switches
  0.726 sq m

(7.8 sq ft)

827 kg

(1825 lbs)

based on cabinet footprint:

1137 kg/sq m (233 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

562 kg/sq m (115 lb/sq ft)

14.06 kg/sq cm

(200 lb/sq in.)