Weight and Floor Loading - Data Mart Appliances

670 Platform Product and Site Preparation Guide

prodname
Data Mart Appliances
created_date
June 2015
category
Product Guide
featnum
B035-5345-112K
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.
Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading