Weight and Floor Loading - Appliance for Hadoop

Appliance for Hadoop 6 Platform Product and Site Preparation Guide

Product
Appliance for Hadoop
Published
February 2018
Language
English (United States)
Last Update
2018-04-13
dita:mapPath
cwt1471885643827.ditamap
dita:ditavalPath
hadoop6.ditaval.ditaval
dita:id
ikf1471650918043
Product Category
Hardware
Vented floor tiles cannot support as much weight as solid tiles. When moving cabinets in a computer room, replace vented floor tiles with solid floor tiles along the path where cabinets will be rolled. Failure to do so may cause damage or collapse of vented floor tiles, resulting in physical damage and/or bodily injury.

Following are the maximum weights for a cabinet containing factory-installed components. Field-installed components may be heavier.

Weight and Floor Loading for Equipment in System
Unit   Actual Footprint Area (No Stabilizers) Approx. Installed Weight Distributed Floor Loading Concentrated Floor Loading
Appliance for Hadoop 6 cabinet maximum configuration:
  • one VMS
  • one KVM
  • eighteen nodes with integrated storage drives
  • two 36-port InfiniBand switches
  • two 24-port server management Ethernet switches
  0.726 sq m

(7.8 sq ft)

820 kg

(1807 lb)

based on cabinet footprint:

1129 kg/sq m (231 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

557 kg/sq m (113 lb/sq ft)

16 kg/sq cm

(227 lb/sq in.)

  0.73 sq m

(7.8 sq ft)

420 kg

(926 lb)

based on cabinet footprint:

578 kg/sq m (119 lb/sq ft)

based on footprint plus servicing clearance required to open doors:

285 kg/sq m (58 lb/sq ft)

8.2 kg/sq cm

(116 lb/sq in.)