Environmental Requirement | Operational | Storage | Transit (Up to 1 Week) |
||
---|---|---|---|---|---|
Temperature (dry bulb) a |
Allowable b: 15° to 32°C (59° to 90°F) Recommended c: 18° to 27°C (64.8° to 80.6°F) |
5° to 45°C (41° to 113°F) |
-40° to 60°C (-40° to 140°F) |
||
Moisture |
Allowable: 20% to 80% (Relative humidity non-condensing) Recommended c: Low end moisture: 5.5°C DP (41.9°F DP) High end moisture: 60% RH and 15°C DP (59°F DP) |
8% to 80% non-condensing |
5% to 95% | ||
Maximum dew point | 17°C (62°F) | 27°C (80°F) | N/A | ||
Maximum altitude b | 3050 m (10,000 ft) | N/A | N/A | ||
Vibration limit |
Operational vibration depends on the type of chassis in the cabinet. The operational vibration limit for a typical node is 0.26G (rms) at 10-500 Hz. The operational vibration limit for a typical disk chassis is 0.28G (rms) at 5-500 Hz. |
N/A | N/A | ||
Static discharge limit | 4000 V direct discharge, 8000 V air discharge | N/A | N/A | ||
a Operating temperature and moisture level is measured at individual chassis inlet. b Due to lower air density at higher altitudes, the maximum dry bulb operating temperature is derated linearly by a value of 3.3° C per 1000 m (1.8° F per 1000 ft) between the altitude of 900 m (2952 ft) and 3050 m (10,000 ft). c The allowable environmental envelope is a statement of functionality of the equipment. The recommended environmental envelope is a statement of reliability—operating equipment near the allowable limits for long periods of time could result in increased reliability issues. |